Menu Close

Water Capillary Mats

Capillary mats - energy transfer device in the room

z DSC08375-555-web (106)

Water capillary mats are the key element of the Hydrokapillare system.

The capillary tubes are made from high quality polypropylene (PP-R) – an environmentally friendly and safe plastic with excellent thermal management and elasticity properties.

Diameter of capillary tubes - 3,4 or 4,3 mm

Basic types of capillary mats:

HK_G_mats_EN

Type G

A - distance between capillaries - 10/20/30/40/60 mm;

B - main pipes PP-R d20x2mm, PN10 (at both ends of the capillary mat)

L - length of capillary mat.

HK_S_mats_EN

Type S

A - distance between capillaries - 10/20/40 mm

B - main pipes PP-R d20x2mm, PN10 (at one end of the capillary mat)

L - length of capillary mat.

Technical data

Material: PP-R (Polypropylene Random Copolymer)
ø  Main pipe:
20 x 2 mm
ø  Capillary tube:
4.3 x 0.8 mm vai 3.4 x 0.55 mm
Distance between capillaries:
10-20-30-40-60 mm
Length: Type S: 600 – 7500 mm

Type G: 600-15000 mm

Width: 150 – 1000 mm
Spec. exchange surface:
0,72 - 1,05 m² / m² capillary mat surface
Spec. weight:
ca. 190 - 880 g / m² capillary mat surface
Spec. water capacity:
0,2 - 0,57 l / m² capillary mat surface
Spec. total weight:
ca. 390 - 1450 g / m² capillary mat surface (without main pipes)
Colour: green, light grey (can be tinted, if necessary)
Maximum temperature in the system: +50° C
Optimal input temperature for heating:
+ 28-32° C
Optimal input temperature for cooling:
+ 16-18 ° C
Optimal pressure in the system: 2-3 bar
Factory test pressure: 20 bar
IMG_1341-555-web
wk_gmats
IMG_1333-555-web
SAM_4841

Additional advantages in safety, maintenance and quality:

  • Limestone does not occur in water capillary mats; limestone forms at +60°C – the water in the water capillary mat system is at max. +32°C for heating and at max. +18°C for cooling.
  • Mud does not occur in water capillary mats; mud results from corrosion – the water capillary mat system uses only corrosion-protected components made from PPR, stainless steel, brass or bronze.
  • Prior to operation, the safety of the water capillary system is verified with air pressure at 20 bar and water pressure at 10 bar; the system is filled only once.
  • Water capillary mats can be easily repaired; a capillary is cut and both ends are welded – with no effect to the heating/cooling output.
  • Water capillary mats do not require maintenance and have a safety guarantee of up to 50 years.